Stromwandler 4fach
Current Transformers for monitoring heat current
The GTZ4121 current transformer acquires heating current and is used in combination with a controller for heat current monitoring. It is capable of transforming up to 4 alternating currents into 4 different direct voltages. The three line currents in 3-phase systems are transformed into a summated voltage when appropriately wired.
Current transformer for top-hat rail mounting for the acquisition of heating current with 4 inputs (1 3-phase current consumer + 1 AC current consumer or 4 AC current consumers)
Input
- 3 or 4 straight-through current transformers, 8.8 mm hole diameter
- 0…40 AAC, 0…20 AAC, 0…10 AAC, 0…5 AAC
- Power consumption: 0.25 W per transformer
Output
- 0…10 VDC, short-circuit proof
Response Characteristics
- Accuracy: 5% of reading
- Output voltage: U=0.2345*I -0.015 (U in V, I in A)
- For mounting to top-hat rail
- Dimensions (LxWxD) 93 x 82.5 x 63 mm