APLUS
Multifunctional Power Monitor with System Analysis
The APLUS is a comprehensive instrument for the universal measurement, monitoring and power quality analysis in power systems.
Condition monitoring
- Provision of all voltages, currents, powers, power factors every 10/12 cycles
- Extended reactive power analysis
- Variance of system variables with time reference
Energy flow analysis
- Power mean-values with trend-analysis for preventing load-peaks
- Load profile storage with fluctuation range (min/max) per interval
- Active /reactive energy class 0.5S (HT/LT, demand/delivery), configurable resolution
- Further mean-values and meters with selectable base quantity
Power quality analysis
- Harmonic analysis acc. IEC 61000-4-7
- Assessment of voltage and current imbalance
- Phasor and phase sequence display for connection check
- Waveform display
- Optional disturbance recorder for PQ events (voltage dip, swell, interruption) acc. IEC 61000-4-30 Ed.3 with RMS1/2 and waveform recordings
Hardware option
Analog outputs ±20mA (2/4), Relay outputs (2), Digital inputs (4) active / passive, GPS time synchronization, Fault-current monitoring (residual or earth current), temperature monitoring (Pt100, PTC), IEC61850 or Profinet I/O
Communication
- Optional: Ethernet (Modbus/TCP, http/https, NTP, SFTP, SYSLOG), IEC61850, Profinet I/O, Modbus/RTU
- Scheduled data export to SFTP server (option Ethernet required)
Security (option Ethernet required)
- Flexible Role Based Access Control
- Encrypted communication via HTTPS
- Audit Log records all security related procedures, support for SYSLOG for transfer to central network monitoring server
- Client whitelist: IP address list for restricting authorized computers
- Digital firmware signature: Prevents that manipulated firmware gets into the device via update
Further features
- 3 current and 3 voltage channels with 0.2% accuracy, direct measurement or via transformers
- Measurement category 600V, CAT III (voltage), 300V,CAT III (current)
- Standard IOs: 1 digital output, 1 digital input/output
- Data logger with16 GB data memory (option)
- Sampling rate: 18kHz
- Monitoring and alarming via limit values and monitoring functions
- For panel mounting 96x96mm
- Identical operation as devices of the PQ/CU/DM series
Possible applications in power systems
- Acquisition and control of the present system state
- Monitoring of the operational behaviour
- Analysis of the power quality
- Determining load profi les and energy demand values
- Finding the variations of the system load
- Measurement before and behind frequency converters
- Recording of operating procedures
The version without display for top hat-rail mounting is intended for applications where no on-site display is needed. It provides the same functionality as a device with display has the same dimensions and connections and may be equipped with the same options.
APLUSVersion with LED display.