SINEAX DM5000
Stationary power monitoring measurement technology for DIN rail mounting (160 x 110 mm)
- Monitoring of grid status and grid asymmetry
- Harmonic analysis in accordance with IEC 61000-4-7
- Threshold monitoring with alarms Multifunc tional DIN rail Do not delete frame, important for production
- Optional PME control center: PME sensors for recording up to 100 currents via radio signal
- Universal process I/O
- Device configuration via web browser
- Cyber security (OT) / cyber protection
- Average power values with trend analysis to prevent load peaks
- Load profile storage with fluctuation range (min/max) per interval
- Active energy class (IEC 62053-22:2003) 0.2S, reactive energy class (IEC 62053-24:2014) 0.5S
- Additional averages and meters with selectable base size
The SINEAX DM5000 is a compact instrument for measuring and monitoring in power distribution systems. It provides a wide range of functionalities which may even be extended by optional components. The connection of the process environment may be performed by communication interfaces, via digital I/Os, analog outputs or relays. The optional display excels in display quality and intuitive operation.
The device may be parameterized via webserver or the optional TFT display (320x240px). No additional software is required.
Hardware options
Up to 2 modular extensions: Analog outputs ±20mA (2/4), Relay outputs (2), Digital inputs (4) active / passive, GPS time synchronization, Fault-current monitoring (residual or earth current), temperature monitoring (Pt100, PTC), IEC61850, Profinet I/O
Communication
- Ethernet (Modbus/TCP, http/https, NTP, SFTP, SYSLOG) and Modbus/RTU
- Optional: IEC61850, Profinet I/O
- Scheduled data export to SFTP server
Security
- Flexible Role Based Access Control
- Encrypted communication via HTTPS
- Audit Log records all security related procedures, support for SYSLOG for transfer to central network monitoring server
- Client whitelist: IP address list for restricting authorized computers
- Digital firmware signature: Prevents that manipulated firmware gets into the device via update
Further features
- 4 current and 4 voltage channels with 0.1% accuracy, direct measurement or via transformers
- Measurement category 600V, CAT III (voltage), 300V,CAT III (current)
- Standard IOs: 1 digital input, 2 digital outputs
- Optional UPS (5×3 minutes)
- Data logger with16 GB data memory (option)
- Sampling rate: 18kHz
- Monitoring and alarming via limit values and monitoring functions
- Device for hat-rail mounting 160x110x70mm
- Identical operation as devices of the PQ/CU/AM series